Euromold Medium voltage epoxy resin equipment bushings
Interface Type | Contact Type | Current Rating (A) | RMS symm. (kA) | Peak asymm. (kA) | Voltage Um (kV) | ||
---|---|---|---|---|---|---|---|
1 sec | 2 sec | 3 sec | |||||
A1 | Pin and socket | 250 | 12.5 | 9 | 7.5 | 31 | 24 |
B1 | Pin and socket | 250 | 12.5 | 9 | 7.5 | 31 | 36 |
B2 | Pin and socket | 400 | 16 | 11.3 | 9.2 | 40 | 36 |
C1 | Bolted | 630 | 28 | 19.7 | 16.1 | 70 | 36 |
C2 | Bolted | 1250 | 75 | 53 | 43.3 | >150 | 36 |
D1 | Bolted | 800 | 50 | 35.3 | 28.8 | 125 | 24 |
D2 | Bolted | 1250 | 75 | 53 | 43.3 | >150 | 24 |
E1 | Bolted | 800 | 50 | 35.3 | 28.8 | 125 | 36 |
E2 | Bolted | 1250 | 75 | 53 | 43.3 | >150 | 36 |
F1 | Bolted | 2500 | - | - | - | - | 36 |
F2 | Bolted | 630 | 28 | 19.7 | 16.1 | 70 | 52 |
F3 | Bolted | 1250 | 75 | 53 | 43.3 | >150 | 52 |